Unreinforced and Reinforced Window and Wall Tie

Two further identical 3m x 3m x 225mm (10ft x 10ft x 9in) solid masonry walls each with a mild steel plate 'window' were constructed. One window used conventional mechanical bolts; the other was strengthened using Cintec Multibar Window anchors. Each wall was subjected to an explosion for a 6kg (18lbs TNT equivalent) charge at 1m (39in) stand off.

Reinforced and Unreinforced Hollow Block (CMU) Wall Test

Reinforced hollow block (CMU) masonry wall. Unreinforced hollow block (CMU) masonry wall.

Two identical 3m x 3m x 225mm (10ft x 10ft x 9in) hollow block (CMU) masonry walls were constructed. One wall was reinforced using Cintec Multibar anchors;

the other was left unreinforced. Each wall was subjected to an explosion from a 6kg (18lbs TNT equivalent) charge at 1.5M (59in) stand off)

 

Blast pressures from small charges near to the target produce very high pressures: Further tests are planned using very large charges at greater standoff.

Post test photo of a cavity wall masonry cube reinforced by Blastec anchors subjected to a blast load from 5kg (11lb) explosives at 1.2m (4ft).

Masonry cube reinforced by Blastec anchors

 
 

 